1.Choose the right battery cells, for different request and dimension, we could select the right battery cells, cylindrical cells or prismatic cells, mainly LiFePO4 cells. Only newly A grade cells used.
2.Grouping the battery with the same capacity and SOC, ensure battery packs have good performance.
3.select the right working current connection busbar, welding the cells at the right way
4.BMS assembly, assemble the right BMS to the battery packs.
5.LiFePO4 battery packs put into the metal Case before testing
6.Product finished
7.Product stacted and ready for packing
8.Wood box Stronger Packing
1.It supports the mixed use of different types.new and old lithium batteries and lithium batteries with different capacities
2. Long battery life (up to 3 times the battery life of a conventional battery)
3.High performance BMS module meets constant current, constant voltage and constant power output.
4.BMS system can accurately detect battery SOC and SOH
5.Multiple anti-theft solutions(optional):software, gyroscope, material.
6.Meet the demand of 57V boost
7.Superior temperature characteristics: the panel adopts die casting
8.Aluminum scheme, self cooling and no noise, and the working temperation
1.home energy storage system battery.
2.telcom power backup.
3.off grid solar system.
4.Energy storage backup.
5.Others battery backup request.
Solar system energy storage
Technical Parameters | Item | Parameters | ||
1.Performance | ||||
Nominal voltage | 48V(adjustable voltage,adjustable range 40V~57V) | |||
Rated capacity | 100Ah(C5 ,0.2C to 40V at 25 ℃ ) | |||
Operating voltage range | 40V-60V | |||
Boost charge/Float charge voltage | 54.5V/52.5V | |||
Charging current (current-limiting ) | 10A(adjustable) | |||
Charging current (Maximum) | 100A | |||
Discharge current (Maximum) | 100A | |||
Discharge cut-off voltage | 40V | |||
Dimensions(WxHxD) | 442x133x450 | |||
Weight | About 4±1kg | |||
2. Function Description | ||||
Installation method | Rack mounted / Wall mounted | |||
Communication interface | RS485*2/Dry contact*2 | |||
Indicator state | ALM/RUN/SOC | |||
Parallel communication | Maximum support for sets of parallel | |||
Terminal stud | M6 | |||
Alarm and protection |
Over voltage, under voltage, short circuit, overload, over
current, over temperature, low temperature protection, etc.
|
|||
3. Working Condition | ||||
Cooling mode | Self-cooling | |||
Altitude | ≤4000m | |||
Humidity | 5%-95% | |||
Operating temperature | Charge:-5℃~+45℃ | |||
Discharge:-20℃~+50℃ | ||||
Recommended operating
temperature
|
Charge:+15℃~+35℃ | |||
Discharge:+15℃~+35℃ | ||||
Storage:-20℃~+35℃ |